Part F ventilation rates: extractor fans and whole dwelling rate

Enter the number of bedrooms, the internal floor area and the wet rooms. The calculator applies Approved Document F (England) to give the minimum whole dwelling ventilation rate, the intermittent extract rate for each room and the continuous rates for a mechanical extract system.

What you enter stays on this device.

Method and sources checked on by the Brikalo editorial team · Our method

The whole dwelling ventilation rate is the minimum fresh air supply for a home, in litres per second. Approved Document F sets it at the higher of a figure by bedrooms (31 l/s for three) and 0.3 l/s per m² of floor area, alongside extract rates of 15 l/s for a bathroom fan.

Three-bedroom home of 90 m² under Approved Document F: the whole dwelling ventilation rate is the higher of 31 l/s (Table 1.3) and 27 l/s (0.3 l/s per m²), so 31 l/s; intermittent extract fans need 30 l/s in the kitchen with a hood extracting outside, 15 l/s in the bathroom and 6 l/s in the WC.

What Approved Document F asks for

Approved Document F, Volume 1: Dwellings (2021 edition) gives the ventilation guidance for homes in England and took effect on 15 June 2022. It asks for three things: extract ventilation in the kitchen, utility room, bathrooms and WCs; a whole dwelling ventilation rate that supplies fresh air to the habitable rooms; and purge ventilation, usually opening windows, in each habitable room.

Rates are in litres per second. Multiply by 3.6 to compare with a fan sold in m³/h: 31 l/s is 111.6 m³/h.

Whole dwelling ventilation rate by bedrooms and floor area

Minimum whole dwelling rate from Approved Document F: the higher of the Table 1.3 figure for the number of bedrooms and 0.3 l/s for each m² of internal floor area, all storeys added together. Example: a three-bedroom house of 90 m² needs 31 l/s, but at 125 m² the floor area rule gives 37.5 l/s.

Bedrooms (Table 1.3)50 m²75 m²100 m²125 m²150 m²
1 bedroom (19 l/s)19 l/s22.5 l/s30 l/s37.5 l/s45 l/s
2 bedrooms (25 l/s)25 l/s25 l/s30 l/s37.5 l/s45 l/s
3 bedrooms (31 l/s)31 l/s31 l/s31 l/s37.5 l/s45 l/s
4 bedrooms (37 l/s)37 l/s37 l/s37 l/s37.5 l/s45 l/s
5 bedrooms (43 l/s)43 l/s43 l/s43 l/s43 l/s45 l/s
6 bedrooms (49 l/s)49 l/s49 l/s49 l/s49 l/s49 l/s

The whole dwelling rate: bedrooms or floor area

The minimum whole dwelling rate must satisfy two conditions, so you take the higher. Table 1.3 gives 19 l/s for one bedroom, 25 for two, 31 for three, 37 for four and 43 for five, plus 6 l/s for each extra bedroom. Paragraph 1.24 adds a floor area rule: 0.3 l/s for each m² of internal floor area, counting every storey.

Example: a three-bedroom house of 90 m² needs the higher of 31 l/s and 0.3 × 90 = 27 l/s, so 31 l/s. A four-bedroom house of 140 m² needs the higher of 37 and 42 l/s: 42 l/s, because the floor area now decides. A home with a single habitable room uses 13 l/s.

Extract rates room by room

Table 1.1 sets the minimum rates for intermittent extract fans, the usual choice when you replace a fan:

  • Kitchen: 30 l/s with a cooker hood extracting to the outside, 60 l/s without one, or with a recirculating hood, which on its own does not count as ventilation.
  • Utility room: 30 l/s.
  • Bathroom: 15 l/s.
  • WC (sanitary accommodation): 6 l/s, or the purge ventilation guidance instead.

For a continuous mechanical extract system, Table 1.2 gives the high rates: kitchen 13 l/s, utility room 8, bathroom 8 and WC 6. The continuous rates of all the extract points together should be at least the whole dwelling rate. In the three-bedroom example with one bathroom and one WC, the high rates add up to 13 + 8 + 6 = 27 l/s, but the continuous total still has to reach 31 l/s.

Special cases

  • Large homes: above five bedrooms, add 6 l/s per bedroom, so six bedrooms give 49 l/s before the floor area check.
  • Two-storey houses: add the ground floor and first floor areas for the 0.3 l/s per m² rule.
  • Fan position: extract terminals and fans, other than cooker hoods, should be as high as practicable and no more than 400 mm below the ceiling.
  • Air paths: internal doors should allow air through, with the free area of a 10 mm undercut in a 760 mm wide door.
  • Wales and Scotland have their own guidance, not covered here.

Common mistakes

  • Fitting a 60 l/s kitchen rate when a cooker hood already extracts outside: 30 l/s is enough in that case, and the reverse mistake is more common.
  • Counting a recirculating cooker hood as extraction.
  • Taking the bedroom figure without checking the floor area rule in a large home.
  • Reading a fan box in m³/h as if it were l/s: 15 l/s is 54 m³/h.

A new fan needs a suitable supply, and better insulation, worked out with the insulation thickness calculator, makes ventilation even more important. Measure each room with the room area calculator, and estimate what the fans cost to run with the electricity usage calculator. If you redecorate the bathroom once the new fan is in, the paint calculator gives the quantity.

Method and sources

References used:

This tool is checked by automated tests against known cases. Spotted a mistake? Report it on the contact page.

Last updated

Frequently asked questions

What extract rate does a bathroom fan need?
15 l/s for an intermittent fan (Approved Document F, Table 1.1), or a high rate of 8 l/s for a continuous system.
What extract rate for a kitchen?
30 l/s with a cooker hood that extracts to the outside, otherwise 60 l/s. A continuous system needs a high rate of 13 l/s.
What is the whole dwelling ventilation rate for a three-bedroom house?
At least 31 l/s, or 0.3 l/s per m² of floor area if that is higher: 31 l/s for 90 m², 37.5 l/s for 125 m².
What extract rate for a WC?
6 l/s, intermittent or continuous. The purge ventilation guidance can be used instead.
How do I convert l/s to m³/h?
Multiply by 3.6: 15 l/s is 54 m³/h and 30 l/s is 108 m³/h.
Does a recirculating cooker hood count?
No. On its own it does not provide ventilation that complies with Part F; the kitchen then needs 60 l/s.
What about a utility room?
30 l/s for an intermittent fan, or a high rate of 8 l/s for a continuous system.